ABB robot 24 kinds of fault maintenance treatment
Release time:
2025-04-14 17:16
Source:
ABB robot 24 kinds of fault maintenance treatment

1. Robot alarm "20252" The motor temperature is high, and DRV1 fault handling
Handling Method: Check whether the motor is overheated, if the temperature of the motor is normal, check whether the connecting cable is normal (it may be that the aviation plug at the control cabinet is not plugged in, if there is no problem, and the robot is in a hurry, the alarm signal can be temporarily shorted, but note that at this time, the motor will not be alarmed after it is really overheated, which may cause the motor to burn out.)
Specific methods of operation: Find the A43 board in the lower left corner of the control cabinet, find the 5 plugs on the board, there are 4 wires on the top, of which the two wires with the wire number 439 and 440 are the motor overheating alarm signal wires to disconnect the two wires from the middle, and the two wires on this side of the board can be shorted.
2.ABB robot power module short-circuit board short-circuit troubleshooting
Human Factors: Hot-swappable hardware is very dangerous, many circuit board faults are caused by hot-swapping, and improper force when plugging and installing board cards and plugs with electricity causes damage to interfaces, chips, etc., resulting in damage to the robot circuit board; As the robot is used for more time, the components on the robot's circuit board will naturally age, which can lead to the failure of the robot's circuit board.
Environmental factors: Due to improper maintenance by the operator, the robot's circuit board is covered with dust, which can cause a short circuit in the signal.
3. When you need to back up your bot
(1) After the new machine is powered on for the first time.
(2) Before making any modifications.
(3) After completing the revisions.
(4) If industrial robots are important, once a week on a regular basis.
(5) It's best to make a backup on a USB flash drive as well.
(6) Backups that are too old are deleted on a regular basis to free up space on your hard drive.
4. Under what circumstances is it necessary to create backups for industrial robots

The above situation is that there is no communication connection between the teach pendant and the robot main controller, and the reasons for the lack of connection include:
(1) The robot host is faulty.
(2) The built-in CF card (SD card) of the robot host is faulty.
(3) Loose network cable between the teach pendant and the host, etc.
Handling Method:
(1) Check whether the host is normal, and check whether the SD card in the host is normal.
(2) Check whether the network cable from the teach pendant to the host is connected properly.
5. What does it mean when the robot appears alarm prompt message 10106 maintenance time reminder?
This situation is a reminder of the intelligent cycle maintenance of ABB robots.
6. How to deal with the robot entering the system fault state when it is turned on?
(1) Restart the bot once.
(2) If not, check the teach pendant to see if there is a more detailed alarm prompt and deal with it.
(3) Restart.
(4) If it still can't be lifted, try to start B.
(5) If that doesn't work, try P launch.
(6) If that doesn't work please try to start (this will bring the robot back to factory settings, be careful).
7. Can robot backup be shared by multiple robots?
No. For example, the backup of robot A can only be used for robot A, not robot B or C, because this will cause system failure.
8. What files can be shared in a bot backup?
If two robots are of the same model and configuration. You can share the RAPID program and EIO files, but they must be verified after sharing before they can be used normally.
9. What is Robot Mechanical Origin? Where is the mechanical origin?
The six servo motors of the robot have a unique fixed mechanical origin, and the wrong setting of the mechanical origin of the robot will cause problems such as limited or misoperation of the robot and inability to walk in a straight line, which will seriously damage the robot.
10. How to remove the robot 50204 action monitoring alarm?
(1) Modify the robot motion monitoring parameters (in the Control Panel - Action Monitoring menu) to match the actual situation.
(2) Use the AccSet command to reduce the acceleration of the robot.
(3) Decrease the v_rot option in the velocity data.
11. How to deal with the alarm "50296SMB memory data difference" when the robot is powered on for the first time?
(1) Select Calibration from the ABB main menu.
(2) Click ROB_1 to enter the calibration screen and select SMB memory.
(3) Select "Advanced" and click on "Clear Control Cabinet Memory" after entering.
(4) Tap "Close" when you're done, and then tap "Update".
(5) Select "Swapped control cabinet or manipulator, update control cabinet with SMB memory data".
12. How to customize the speed of the robot trajectory movement in the RAPID program?
(1) In the main menu of the teach pendant, select Program Data.
(2) Once you have found the data type Speeddata, click New.
(3) Click on the initial value, the meaning of the four variables of Speeddata is as follows: v_tcp represents the linear running speed of the robot, v_rot represents the rotating running speed of the robot, v_leax represents the linear running speed of the external axis, and v_reax represents the rotating running speed of the external axis.
(4) The customized data can be called up in the RAPID program.
13. How to deal with motor error and counter overflow error when rotating at high speed?
When rotating at high speed, there is a motor error and the counter overflows the error.
Solution 1:
Check whether the wiring of the motor power cables and encoder cables is correct and whether the cables are damaged.
When entering a long command pulse, a motor error occurs and the counter overflows the error.
During operation, there was a motor error, and the counter overflowed the error.
Solution 2:
Increase the error counter overflow level setpoint; Slow down the rotation; Extend acceleration and deceleration times; If the load is too heavy, it is necessary to select a motor with a larger capacity from scratch or reduce the load, and install a reducer and other transmission organizations to improve the load capacity.
14. It doesn't work when there is a pulse output, how to deal with it?
Supervise the pulse output value of the controller at that time and whether the pulse output light is flashing, and admit that the command pulse has been fulfilled and the pulse is now output normally;
Check whether the control cable, power cable, and encoder cable from the controller to the drive are faulty, damaged, or poorly contacted;
Check if the brakes of the servo motor with the brake are now turned over;
The panel that supervises the servo drive acknowledges whether the pulse command is entered;
The Run command is normal;
The control form must be selected in the direction control form;
whether the input pulse type set by the servo drive and the setting of the command pulse are common;
Make sure that the forward side drive stop, the swing side drive stop signal and the error counter reset signal are not entered, the load is disconnected and the no-load operation is normal, and the mechanical system is checked.
15. There is no overload report with load, how to deal with it?
If the servo Run signal is connected and there is no pulse:
Check the wiring of the servo motor power cable to see if there is any poor contact or broken cable; In the case of a servo motor with a brake, the brake must be flipped open; whether the speed loop gain is set too large; Whether the integration time constant of the velocity loop is set too small.
If the servo is only in operation:
whether the gain of the azimuth loop is set too large; Whether the positioning completion amplitude is set too small; See that there is no stall on the servo motor shaft and adjust the machinery from scratch.
16. How to deal with abnormal sound or flutter during operation?
Servo wiring:
Servo parameters:
The servo gain setting is too large, and it is advocated to adjust the servo parameters from scratch by manual or active methods; Acknowledging the setting of the time constant of the velocity response filter, the initial value is 0, and the setting value can be increased by testing; The electronic gear ratio is too large for the setting, and it is advocated to restore to the factory settings; The resonance of the servo system and the mechanical system, test and adjust the frequency and amplitude of the notch filter.
Mechanical system:
The coupling connecting the motor shaft and the equipment system is offset, and the mounting screws are not tightened; Poor occlusion of pulleys or gears will also lead to load torque changes, test no-load operation, if no-load operation is normal, then check whether the joint part of the mechanical system is abnormal; Acknowledging whether the load inertia, torque and rotational speed are too large, testing no-load operation, and if no-load operation is normal, lightening the load or replacing a larger capacity drive and motor.
17. How to deal with the inaccurate positioning of ABB servo motor repair?
First of all, admit whether the actual pulse value announced by the controller is the same as expected, if not, check and correct the program, supervise whether the number of pulse instructions received by the servo driver is common with the number of pulse instructions announced by the controller, and check the control line and cable if not; Check whether the settings in the form of the servo command pulse are the same as those set by the controller, such as CW/CCW or pulse direction;
The servo gain setting is too large, and the test adjusts the servo gain from scratch with manual or active methods; The servo motor is prone to accumulate errors when carrying out reciprocating motion, and it is advocated to set a mechanical origin signal under the condition of process consent, and carry out the origin finding operation before the error exceeds the promised scale; The accuracy of the mechanical system itself is not high or the transmission structure is abnormal (such as the coupling part between the servo motor and the equipment system is offset, etc.).
18. How to deal with the overspeed fault of servo motor repair and azimuth control?
As soon as the servo Run signal is connected, it will occur: check whether the wiring of the servo motor power cable and encoder cable is correct and whether there is any damage.
19. How does ABB robots perform routine maintenance?
"Brake Inspection" Before normal operation, it is necessary to check the motor brake for each shaft of the motor brake inspection method as follows:
(1) Run the axis of each robot to the position where it has the greatest load.
(2) The motor mode selector switch on the robot controller hits the MOTORS OFF position.
(3) Check whether the shaft is in its original position, if the manipulator still maintains its position after the motor is turned off, it means that the brakes are good.
The danger of losing the function of deceleration operation (250mm/s).
Do not change the gear ratio or other motion parameters from the computer or the teach pendant. This will affect the deceleration run (250mm/s) function.
20. Points to note when using a teach pendant safely:
The Enabling device button mounted on the teach pendant changes to MOTORS ON mode when pressed halfway. When the button is released or pressed in its entirety, the system changes to MOTORS OFF mode.
21. In order to use the teach pendant safely, the following principles must be followed:
(1) When the enabling device button cannot be programmed or debugged, the enabling device button is immediately released when the robot does not need to move.
(2) When the programmer enters the safe area, the teach pendant must be carried with them at all times to prevent others from moving the robot.
22. The following points are observed when working within the working range of the manipulator
(1) The mode selector switch on the controller must be in the manual position in order to operate the enabling device to disconnect the computer or remote control;
(2) When the mode selector switch is on
(3) Pay attention to the rotating axis of the manipulator and watch out for hair or clothing stirring on it. In addition, pay attention to other optional parts or other equipment on the manipulator;
(4) Check the motor brakes for each axle.
23. Touch deviation
Phenomenon 1: The position of the finger does not coincide with the mouse arrow.
Cause: After the teach pendant has installed the driver, there is no vertical touch to the bullseye center position when correcting the position.
Solved: Recalibrate the position.
Phenomenon 2: The touch in some areas is accurate, and the touch in some areas is biased.
Cause: A large amount of dust or scale has accumulated on the sound wave reflection stripes on the four periphery of the surface sound wave touch screen, which affects the transmission of sound wave signals.
Solution: Clean the touch screen, pay special attention to clean the sound wave reflection stripes on the four sides of the touch screen, and disconnect the power supply of the touch screen control card when cleaning.
24. The teach pendant does not respond to the touch
Phenomenon: When touching the screen, the mouse arrow does not move, and the position does not change.
Causes: There are many reasons for this phenomenon, which are as follows:
(1) The dust or scale accumulated on the sound wave reflection stripes on the four periphery of the surface acoustic touch screen is very serious, resulting in the touch screen not working;
(2) The touch screen is malfunctioning;
(3) The touch screen control card is faulty;
(4) The touch screen signal line is faulty;
(5) The serial port of the host computer is faulty;
(6) The operating system of the teach pendant is malfunctioning;
(7) Touchscreen driver installation error.
Solution: Observe the touchscreen signal indicator, which flashes regularly under normal conditions, about once per second.
When touching the screen, the teach pendant is black, and this problem is more complicated. If the backlight is set to save money, a black screen is normal; If you mismanipulate the second word in the system control area, the screen will also be black. If the first two points are excluded, update to the latest firmware for viewing.